ASTM F1116-14a: Test method to determine the “Dielectric Strength” of dielectric overfoot and overshoe footwear:

This document is not an official reproduction of the standard; refer to the standards issued by ASTM https://www.astm.org

Apparatus:

The boot is filled with water or other conducting media up to a distance (h) from the top of the upper.

The boot is immersed in water or other conducting media up to the same distance (h) from the top of the upper.

The high voltage source is connected to the metal beads inside the boot.The water in the tank around the boot is connected to the ground.

  AC test   DC test
Voltage (rms value)  h (mm)  Voltage (avg value)   h (mm)
 15 000 V  63.5  45 000 V  76
 20 000 V  76  60 000V  89


The water or other conducting media inside the footwear shall be connected to one terminal of the voltage source. The water or other conducting media outside the footwear shall be connected to one terminal of the voltage source

Testing voltage is applied during 1 to 3 minutes.

No flashover between electrodes is permitted during testing.

No breakdown shall ocure during testing.

ASTM F1116 dielectric test method